Daikin Perfera RXM R Series Service Manual page 101

Split r32
Table of Contents

Advertisement

RXM20~71R + ARXM25~71R + FTXM20~71R + ATXM25~50R +
FVXM25~50A
Split New Perfera R32
ESIE20-11 – 2021.01
a
a
a Hook (left side)
b Hook (right side)
c Indoor unit heat exchanger
6 Route the fan motor ground wire in front of the indoor unit heat exchanger.
7 Carefully move the indoor unit heat exchanger to the correct position and
install it on the 2 hooks on the left side.
8 Connect the ground wire to the indoor unit heat exchanger using the screw.
c
a
b
a Screw (plate)
b Plate
c Indoor unit heat exchanger
d Piping fixture
e Flared joint
f Screw (ground wire)
9 Make sure that the refrigerant field piping connections are clean and not
damaged. Remove the caps and properly connect the field piping to the liquid
and gas pipes of the indoor unit. Tighten the flared joints.
10 Correctly install the insulation on the liquid and gas pipes. Install the piping
fixture.
11 Install the plate in the correct location on the indoor unit heat exchanger.
Install and tighten the screw to fix the plate.
12 Install the lower air outlet assembly in the correct location. Install and tighten
the 2 screws.
c
b
b
f
d
3
Components
|
e
e
Service manual
101