11.6 Input Terminal Function

• Table of input terminal functions 1
Function
Code
No.
0,1
-
2
F
3
FN
4
R
5
RN
6
ST
7
STN
8
RES
9
RESN
10
SS1
11
SS1N
12
SS2
13
SS2N
14
SS3
15
SS3N
16
SS4
17
SS4N
18
JOG
19
JOGN
20
EXT
21
EXTN
22
DB
23
DBN
24
AD2
25
AD2N
28
VF2
29
VF2N
32
OCS2
33
OCS2N
36
PID
37
PIDN
48
SCLC
49
SCLCN
50
HD
51
HDN
52
IDC
53
IDCN
54
DR
55
DRN
Function
No function
Forward run command
Inversion of forward run command
Reverse run command
Inversion of reverse run command
Standby
Inversion of standby
Reset command
Inversion of reset command
Preset-speed command 1
Inversion of preset-speed command 1
Preset-speed command 2
Inversion of preset-speed command 2
Preset-speed command 3
Inversion of preset-speed command 3
Preset-speed command 4
Inversion of preset-speed command 4
Jog run mode
Inversion of jog run mode
Emergency stop by external signal
Inversion of emergency stop by external signal
DC braking command
Inversion of DC braking command
2nd acceleration/deceleration
Inversion of 2nd acceleration/deceleration
2nd V/F control mode switching
Inversion of 2nd V/F control switching
2nd stall prevention level
Inversion of 2nd stall prevention level
PID control prohibition
Inversion of PID control prohibition
Forced local from communication
Inversion of forced local from communication
Operation hold (hold of 3-wire operation)
Inversion of operation hold (hold of 3-wire operation)
PID integral/differential clear
Inversion of PID integral/differential clear
PID characteristics switching
Inversion of PID characteristics switching
K-17
Action
Disabled
ON: Forward run, OFF: Slowdown stop
Inversion of F
ON: Reverse run, OFF: Slowdown stop
Inversion of R
ON: Ready for operation,
OFF: Coast stop (gate OFF)
Inversion of ST
ON: Acceptance of reset command,
ON
OFF: Trip reset
Inversion of RES
Selection of 15-speed SS1 to SS4 (SS1N to
SS4N) (4 bits)
ON: Jogging mode (fixed at 5Hz),
OFF: Jog run canceled
Inversion of JOG
ON:  trip stop
Inversion of EXT
ON: DC braking, OFF: Brake canceled
Inversion of DB
ON: Acceleration/deceleration 2,
OFF: Acceleration/deceleration 1
Inversion of AD2
ON: 2nd V/F control mode
(V/F fixed,  , , , )
OFF: 1st V/F control mode
( setting, , , , )
Inversion of VF2
ON: Enabled at the value of 
OFF: Enabled at the value of 
Inversion of OCS2
ON: PID control prohibited
OFF: PID control enabled
Inversion of PID
Enabled during communication
ON: Local (Setting of , )
OFF: Communication
Inversion of SCLC
ON: F (forward run), R: (reverse run) held, 3-wire
operation
OFF: Slowdown stop
Inversion of HD
ON: Integral/differential clear, OFF: Clear canceled
Inversion of IDC
ON: Inverted characteristics of  selection
OFF: Characteristics of  selection
Inversion of DR
E6581595