Configuring Steady, Pulse and One Shot Mode
• Steady and Toggle Modes: These modes are not affected by the Time Base and Time Multiplier parameters below.
• Pulse Modes: The system calculates the On Time (activation) and the Off Time for outputs based on the values in the Base
and Multiplier columns (see Table 34 ). The duration, or On Time, of an output is determined by selecting one of the four
Base options from Table 34 . Calculate the Off Time by multiplying the Base by the Multiplier.
The Time Base of 200 ms in Table 34 and Table 35 is only available for on-board outputs.
Base
0
1 (200 ms)
2 (1 sec)
3 (1 min)
4 (1 hr)
• One Shot Modes: The duration of the On Time of a One Shot output is determined by multiplying the Base by the Multiplier.
Base
1 (200 ms)
2 (1 sec)
3 (1 min)
4 (1 hr)
Page 94
P/N: 4998152533-02
PART IV: CONTROL PANEL PROGRAMMING
On Time
(On Time = Time of Base)
0
200 ms
1 sec
1 min
1 hr

Table 34: Pulse Mode Configuration

Multiplier
0
N/A
01-99
01-99
01-99
01-99

Table 35: One Shot Mode Configuration

Copyright  2007 Bosch Security Systems, Inc.
Multiplier
Off Time
(Off Time = Base x Multiplier)
N/A
Always Off
01-99
200 ms – 19.8 sec
01-99
1 – 99 sec
01-99
1 – 99 min
01-99
1 – 99 hr
On Time
(On Time = Base x Multiplier)
0
200 ms – 19.8 sec
1 sec – 99 sec
1 min – 99 min
1 hr – 99 hr
Tolerance
N/A
±200 ms
±1 sec
±1 min
±1 hr
Tolerance
N/A
±200 ms
±1 sec
±1 min
±1 hr
DS7200V2-UK Installer's Guide