DX2010 Tamper Input Connections

Each DX2010 module provides an input for tamper
devices. The tamper input is in addition to the zone
sensor loops. Supervising an enclosure tamper does
not deplete a zone. A fault on the tamper input
reports as a tamper using the DX2010's address.
The tamper output can monitor external Normally
Closed (N/C) tamper switches when wired as shown
in Figure 24. The tamper circuit must be closed to
provide proper Input Expander tamper supervision to
the control panel. Do not use an EOL resistor.
The DX2014 also provides an on-board tamper
switch. The cover tamper spring is supplied with the
DX2014.
The DX2013's on-board tamper switch cannot be
used since it is mounted inside the control panel's
enclosure (wire the tamper input as shown in Figure
25 if installed in the control panel's enclosure).
If neither the tamper input nor the on-board tamper
switch is used, a wire jumper must be placed as
shown in Figure 25.
Use either the tamper input or the on-board tamper
switch. Both cannot be used simultaneously.
On-board
tamper switch
+OUT-

Figure 24: DX2010 Tamper Input Wiring

On-board
tamper switch
+OUT-

Figure 25: DX2010 Wire Jumper Connections

DS7200V2-UK Installer's Guide
DX2010
TMPR
R
B
G
Y
1
COM
DX2010
TMPR
R
B
G
Y
1
COM
Copyright  2007 Bosch Security Systems, Inc.
18.6

DX2010 Tamper-wired Configuration

For tamper-wired sensor loop configuration, wire as
shown in Figure 26.
1
COM
2
3
COM
Tamper
Tamper
Contact
Contact
2.2 k EOLs
2.2 k EOLs
Alarm Contacts

Figure 26: DX2010 Tamper-Wired Loop Configuration

18.7

DX2010 Addressing

Any time the address DIP switches are
changed, you must cycle the power to the
module OFF and then ON for the changes
to take effect.
Each DX2010 connected to the control panel must
have its address jumpers set to the addresses shown
in Table 7. Shaded cells only apply to the DS7240V2.
Location #
Standard Sensor Loop*
1 to 8
9 to 16
17 to 24
25 to 32
33 to 40

Table 7: DX2010 Address Settings

• For Standard Sensor Loop, set Location's "Device"
parameter to "2." Set the DX2010 Address as
shown in Table 8. See Location ##, Device on page
74 for programming details.
For tamper-wired zones, use Data Bus Addresses
101-105. Set the device type settings to "2" (see
Location ##, Device on page 74).
PART II: SYSTEM INSTALLATION AND SETUP
4
5
COM
6
7
COM
8
Data Bus Address 101
Data Bus Address 102
Data Bus Address 103
Data Bus Address 104
Data Bus Address 105
P/N: 4998152533-02