Dacm Supervision; System Power Up; System Status Led; Figure 54: Dacm To Control Panel Wiring - Bosch DS7200V2-UK Installer's Manual

Table of Contents

Advertisement

You can use either one of the Aux Power (-) terminals
and either one of the 12 VDC (+) terminals when
connecting devices to the control panel.
DACM

Figure 54: DACM to Control Panel Wiring

You can use either one of the Aux Power (-) terminals
when connecting devices to the control panel.
Do not tie the black (-) output to earth ground
when using any external power supply. A
ground fault condition is reported if black (-)
is grounded.
DACM
Red (+)
(+)
(-)
12 VDC
External Power Supply

Figure 55: DACM to External Power Supply Wiring

22.3

DACM Supervision

The control panel supervises communication to the
DACM. If the control panel fails to communicate with
the DACM, it sends a "Dbus Missing" {125} report.
Page 32
P/N: 4998152533-02
PART II: SYSTEM INSTALLATION AND SETUP
Control Panel
Green
Yellow
Black (-)
Red (+)
BATT+
BATT-
Control Panel
Green
Yellow
Black (-)
Bat+
Bat-
Copyright  2007 Bosch Security Systems, Inc.
23.0

System Power Up

The system shows a trouble upon any power-up
because the date and time settings are missing. This
trouble remains until these settings are made.
To reduce the occurrence of false alarms
upon control panel power-up (or restoration
of power after a complete loss of primary and
secondary power), the control panel ignores
all zone faults for approximately 60 seconds
while the devices stabilize.
24.0

System Status LED

The System Status LED shows system status,
including power supply status as described below.
Figure 56 shows the location of the control panel's
LED.
STATUS
PO1 SELECT
BATT+
BATT-
ALRM
PO1
SMK
A
B
L-1
+
+

Figure 56: System Status LED

System Status LED Operation
System Normal
Battery Missing
AC Missing
Phone Ringing
Phone Line Seized (panel
using phone line)
Shut Down (system voltage
below 10.2 VDC)

Table 18: System Status LED Operation

Status LED
AUXILIARY
COM
L-2
L-3
COM
L-4
L-5
COM
L-6
L-7
COM
L-8
On for 50 ms, off for 1 sec.
Off for 200 ms, on for 1 sec.
Off for 200 ms, on for 200 ms,
off for 200 ms, on for 1 sec.
Flickers for 1 sec. As each
ring is detected.
On solid.
Off for 200 ms, on for 200 ms,
off 200 ms, on 200 ms, off
200 ms, on for 1 sec.
DS7200V2-UK Installer's Guide