P## Audible After 2 Failures; P## Invisible; P## Buz On Fault; P## Watch Point - Bosch D9112B Program Entry Manual

Control panel
Table of Contents

Advertisement

D9112B | Program Entry Guide | 7.0

P## Audible After 2 Failures

Use with non-fire points programmed for "silent
bell" to provide local alarm bell output in the event
that the panel cannot send the
The amount of time and pattern of the relay
activation is programmed by an area in Bell
A# Burg Time
Parameters.
at least four minutes. To allow time for reporting
attempts. The bell timer starts when the alarm trips,
but the bell output starts only after two failed
attempts by the panel to communicate the report.
Default:
No
Selection:
Yes or No
Yes
When this point goes into alarm, if the
D9112 fails after two attempts to
communicate the report, it activates
the relay programmed to provide
alarm output for the area where the
point is assigned.
No
Points programmed for silent bell: do
not activate the alarm relay if the
panel cannot send the

P## Invisible

Default:
No
Selection:
Yes or No
Yes
Command centers do not display
alarm activity from this point. This
option is designed for use with hold-
up devices. Typically, an invisible
point is NOT programmed to activate
the "buzzer on fault." Often invisible
points are not programmed to create
audible alarms, but instead provide a
silent alarm output. Alarm events
from invisible points can be viewed or
printed using the event log.
The "relay follows point" option does
not work for invisible points. Do not
use this feature with invisible points.
No
Activity from this point is visible at
the command centers.

P## Buz on Fault

The "buzz on fault" option allows the point to
generate a tone for any fault condition (open, short,
or missing). Some common applications for this
option are: annunciation of emergency exits during
business hours, and pool gates.
Bosch Security Systems | 2/04 | 74-06145-000-D
Point Index
Alarm
report.
must be programmed for
Alarm
report.
Default:
No
Selection:
Yes or No
Yes
Sound the command center buzzer for
any fault on this point.
If this is a
does not silence the tone. To silence
the tone, the point must be restored to
normal.
If this is a non-fire point,
COMMAND 4 or a passcode can
silence the tone. CHECK DEVICE
displays until the point is restored to
normal.
No
Do not sound the command center
buzzer for fault conditions. Only
specific trouble conditions as
programmed in
generate a trouble buzzer.

P## Watch Point

Default:
No
Selection:
Yes or No
Yes
This point activates Watch Mode
responses if it is faulted while the
panel is in Watch Mode. Alarm and
Trouble responses override Watch
Mode responses.
No
Do not activate Watch Mode
responses for this point.
EN | 74