P## Audible After 2 Failures; P## Invisible Pt - Bosch D9412G Program Entry Manual

Table of Contents

Advertisement

D9412G/D7412G | Program Entry Guide | 4.0 RADXPNTS
If the point restores and the fire alarm is
not silenced from the command center,
the fire alarm output continues until Fire
Bell time expires. If the point does not
restore, the fire alarm output continues
even after bell time expires.
\
Use this option for fire applications to meet
the requirement that audible alarms cannot
be silenced until the fault condition clears
or the Fire Bell time expires.

P## Audible After 2 Failures

Default:
No
Selection:
Yes or No
Yes
A# Burg Alarm relay activates after two
failed attempts.
No
P## Silent points do not cause the A#
Burg Alarm relay to activate even if the
report does not get to the central
station receiver.
Use this option for reporting Non-fire points
P## Silent
programmed as
alarm bell to ring if the control panel fails to report
the Alarm Event at the end of two failed attempts to
the remote central station receiver.
0101
When a point that is programmed for P##
0101
Silent Bell is faulted, the timer for the A#
0101
Burg Time starts, even though the bell is
not yet ringing. It can take up to 3 minutes
before the second attempt fails. Ensure A#
Burg Time is programmed to provide the
amount of bell time you need, minus the 3
minutes it can take before the bell actually
begins to ring.

P## Invisible Pt

Program Record Sheet
Default:
See
Selection:
Yes or No
Yes
Command centers do not display
alarm activity from this point.
No
Activity from this point is visible at the
command centers.
Use this option to determine whether the point
appears in the command center display upon an
Alarm condition. For LED command centers, the
LED does not illuminate upon an alarm condition.
Point text appears and annunciation is made for
Invisible points programmed for a trouble condition
in point response.
Bosch Security Systems | 10/03 | 47775E
to eventually cause the
To prevent the command center alarm tone
and the A# Burg Alarm bell from sounding,
this point needs P## Silence Bell
programmed as Yes.
0101
ALARM SILENCED displays at the
0101
command center if this Invisible point
0101
causes a bell to ring upon an alarm and a
valid passcode is entered.
EN | 84