Attaching Cables
You can only attach one or two shielded cables per shield terminal (see figure and table
above). The cable is connected by its bare cable shield. There must be at least 20 mm of
bare cable shield. If you need more than 4 shield terminals, start wiring at the rear row of the
shield contact element.
Note
Use a sufficiently long cable between the shield terminal and the front connector. This
enables you to remove the front connector without removing the shield terminal.
ET 200M
Operating Instructions, 12/2008, EWA-4NEB780600602-08
5.4 Wiring the power supply and modules
Connecting
87