Table 9- 9
Error type of the channel-related diagnostic - manufacturer-specific
Error type
Error text
10000
16
Parameter
B
D
configuration
error
10001
17
Encoder or load
B
D
voltage missing
10010
18
Fuse faulty
B
D
10011
19
Communication
B
D
error
10100
20
Ground error
B
D
10101
21
Reference
B
D
channel fault
10110
22
Hardware
B
D
interrupt lost
10111
23
Warning
B
D
11000
24
Switch off
B
D
11001
25
fail-safe switch
B
D
off
11010
26
External error
B
D
11011
27
Unclear error
B
D
11100
28
reserved
B
D
ET 200M
Operating Instructions, 12/2008, EWA-4NEB780600602-08
Meaning
Parameter configuration error, e.g.:
Module cannot evaluate the parameter (unknown,
•
inadmissible combination, ...)
Module not configured
•
User calibration does not correspond to the configuration
•
Calibration error
•
The following voltages could me missing:
external supply voltage
•
Voltage to operate the module
•
The user´s exchangeable fuse has failed
With F technology (PROFIsafe):
Error with the consecutive number (sign of life)
•
Error in the user data CRC
•
User data timeout
•
Ground error, e.g.:
The permissible common mode voltage for isolated
•
channels has been exceeded
The M line is broken in the case of isolated channels
•
Error on the reference channel
Hardware interrupt has become lost
There could be a warning, if limit values like:
Speed
•
Load current
•
are exceeded
There could be a switch off:
Power switch is triggered on account of short circuit,
•
asymmetry, contact to earth
Thermistor triggered
•
Quick stop
•
fail-safe switch off
•
Trigger / cause for fail-safe switch of is given
External (process-side) error, e.g.:
Sensor error
•
Actuator error
•
Sensor data is incorrect
•
Unclear errors are those that are not specified in any more
detail
Interrupt, error and system messages
9.1 PROFIBUS DP
Remedy
Correction of the
parameterization
Correction of the
process wiring
Replace the fuse
Check the
communication paths
Correction of the
process wiring
Replace the reference
channel module
Correction tuning of
program /
process / module
Correction tuning of
program /
process / module
Remedy the cause of
switch off and
acknowledge
Remedy the cause of
switch off
Replace sensor /
actuator / correct
process wiring
different, depending on
cause of error
203