Interrupt, error and system messages
9.1 PROFIBUS DP
LEDs
SF
BF
ON
on
off
on
inadmissible PROFIBUS address
Is the SF LED of an SM / FM also lit?
off
off
on
There is data exchange between the DP
master and the ET 200M.
The preset configuration and actual
configuration of the ET 200M match.
* not relevant
Status and error displays of the IM 153-2
Table 9- 2
LEDs
SF
BF /
ACT
BF1
off
off
off
*
*
*
on
off
off
on
on
on
on
on
off
off
flashes
off
at
0.5 Hz
on
flashes
off
at
0.5 Hz
on
flashes
off
at
2 Hz
186
Meaning
If so: Error or diagnosis in an S7 300
module
If not: IM 153-1 is faulty.
ON
off
No voltage on the IM 153-2 or there is a
hardware fault with the IM 153-2.
on
There is voltage on the IM 153-2.
IM 153-2 is functioning.
off
IM 153-2 is undergoing a hardware reset
after switching on
on
Hardware test after switching on
off
The operating system update is running
off
The operating system update has
concluded successfully
off
external error, e.g. unsuitable operating
system or SIMATIC Micro Memory card
off
internal error, e.g. when writing the update
files
On the IM 153-1 set a valid PROFIBUS address (1
to 125)
Check the SM / FM with the diagnostics. Replace
the S7-300 module or the IM 153-1 or contact your
Siemens representative.
Meaning
Operating Instructions, 12/2008, EWA-4NEB780600602-08
Remedy
Remedy
Switch on the power supply module or
replace the IM 153-2.
with IM 153-2Bx00:
remove the SIMATIC Micro Memory
card and switch off the IM 153-2.
Use a suitable operating system for the
update.
Do not remove the SIMATIC Micro
Memory card during the update (only
with IM 153-2Bx00).
Repeat the update process.
If the LEDs indicate an error, the
internal memory is faulty.
ET 200M