Download Print this page

Siemens SIMATIC ET 200M Operating Instructions Manual page 231

Distributed i/o device
Hide thumbs Also See for SIMATIC ET 200M:

Advertisement

Use in residential areas
If you use the ET 200M in residential areas, you must ensure that the radio interference
emissions comply with limit value class B in accordance with EN 55011.
The following measures are recommended to ensure the interference complies with limit
value class B:
● Install the ET 200M in grounded switching cabinets/boxes
● Use of noise filters in the supply lines
Laser protection classes authorization (for the IM 153-2 FO)
Class 1 in accordance with EN 60825-1: 1994+A11: 1996 or IEC 60825-1: 1993 including
amendment 1:1997
In the case of an intentional / unintentional opening of the accessible FOC radiation in
accordance with degree of endangering 1 as per EN 60825-2: 1994 or IEC 60825-2: 1993.
10.2
Parameters of the IM 153-x
Parameter assignment
You configure the IM 153-x or the ET 200M with
different configuration tool, you must integrate the GSD file.
Table 10- 2
Parameters of the IM 153 x
Parameters
DPV1 mode
Start up at preset ≠ actual
configuration?
"Module change during
operation"?
Diagnostic Interrupt
Process interrupt
Removing / insertion interrupt
Analog-value format
ET 200M
Operating Instructions, 12/2008, EWA-4NEB780600602-08
WARNING
There is a risk of injury or of damage to assets.
In potentially explosive environments, there is a risk of injury or damage if you
disconnect any connectors while the ET 200M is in operation.
In explosive environments, always isolate the ET 200M before you disconnect
connectors.
Range of values
block / enable
yes/no
yes/no
block / enable
block / enable
block / enable
SIMATIC S7 / SIMATIC S5
10.2 Parameters of the IM 153-x
STEP 7
COM PROFIBUS
or
Default
Scope
enable
ET 200M
No
ET 200M
No
ET 200M
enable
ET 200M
enable
ET 200M
enable
ET 200M
SIMATIC S7
ET 200M
Technical Specifications