Technical Specifications
10.4 Technical specifications of the IM 153-4 PN interface module
Rated supply voltage of electronics (L+)
•
•
Galvanic isolation
•
•
•
Permissible potential difference (relative to rail)
Insulation test voltage
Current consumption from rated supply voltage
(L+)
Current consumption from backplane bus
Power loss of the module
Interrupts
Diagnostic function
•
•
•
•
•
•
238
Incorrect polarity protection
Voltage failure bypass
Between the backplane bus and electronic
components
Between Ethernet and electronic components
Between the supply voltage and electronic
components
Group error
Bus monitoring PROFINET IO
Monitoring of the supply voltage of the
electronics
Maintenance requirement (maintenance)
Existing connection to network
Transmitting / receiving data on the network
Voltages, currents, potentials
24 VDC
yes
Min. 5 ms
No
yes
No
75 VDC / 60 VAC
500 VDC
max. 600 mA
Max. 1.5 A
max. 6 W
Status, alarms, diagnostics
yes
yes
Red LED "SF"
Red "BF" LED
Green "ON" LED
yellow "maint" LED
One green "LINK" LED per port
One yellow "RX/TX" LED per port
Operating Instructions, 12/2008, EWA-4NEB780600602-08
ET 200M