2.1.5
Configuring the ET 200M in the SIMATIC manager
Procedure
1. Start the SIMATIC Manager and then set up a new project with a DP master (e.g. CPU
2. From the hardware catalog, insert the IM 153-2 on the PROFIBUS DP.
3. Set the PROFIBUS address 3 on the IM 153-2.
4. Drag the individual modules out of the hardware catalog and drop them onto the
ET 200M
Operating Instructions, 12/2008, EWA-4NEB780600602-08
315-2 DP). In addition to OB 1 also create OB 82 for the project.
configuration table.
Figure 2-4
Configuration table for ET 200M
Brief instructions on commissioning
2.1 Commissioning on PROFIBUS DP
27