Download Print this page

Siemens SIMATIC ET 200M Operating Instructions Manual page 222

Distributed i/o device
Hide thumbs Also See for SIMATIC ET 200M:

Advertisement

Interrupt, error and system messages
9.2 PROFINET IO
LEDs
SF
BF
MT
off
off
*
on
on
*
off
Flash
*
es at
0.5
Hz
on
Flash
*
es at
0.5
Hz
on
Flash
*
es at
2 Hz
*
*
on
LINK
RX/TX
off
off
on
on
on
* not relevant
9.2.2
Diagnostic messages of the electronic modules
Actions after a diagnosis message
Every diagnostic message leads to the following actions:
● The SF LED on the interface module is lit.
● There can be more than one diagnostic message at the same time.
● Diagnostics data are reported as diagnosis interrupts and can be read from data records.
● Following a diagnostic message, the message is saved in the diagnostic buffer of the I/O
● Next, OB 82 will be called. If OB 82 is not available, the I/O controller goes to STOP
● Acknowledgment of the diagnostic interrupt to enable new interrupts.
220
ON
on
Data exchange is taking place between
the
IO controller and the ET 200M.
The preset configuration and actual
configuration of the ET 200M match.
off
FW update busy
off
FW update successfully completed
off
external error during FW update
(incorrect FW, for example)
off
internal error during FW update
(possible read/write error)
Loss of synchronization
on
Network error
There is no connection to the IO controller
(no IO controller available on the network)
*
Autonegotiation completed and
PROFINET transmission rate accepted
Transmission/reception is in progress
controller.
mode.
Meaning
Operating Instructions, 12/2008, EWA-4NEB780600602-08
Remedy
Use the correct FW for the update.
Repeat the FW update.
Also see Maintenance interrupts
(Page 222)
No uniform transmission rate
Autonegotiation not successful
ET 200M

Hide quick links:

Advertisement

loading

This manual is also suitable for:

Im 153-1Im 153-2Im 153-2 foIm 153-4 pn