8.2.2.3
Time synchronization for time stamping
Requirements
The following requirements apply to the time synchronization for time stamping:
● There must be a clock master, e.g. SICLOCK TM available in the automation system. It
● The time message frame must be forwarded:
● For the IM 153-2 (as of 6ES7153-2BAx1-0XB0) a synchronization interval of 10 s must be
Time synchonrization for highly precise time stamping with 1 ms precision
You must realize the time synchronization for the highly precise time stamping with the
following hardware components and settings:
● Time master: SICLOCK TM (as of FW V3.3.0090) with GPS synchronization
Synchronization /
Redundancy
Inputs
Ethernet
ET 200M
Operating Instructions, 12/2008, EWA-4NEB780600602-08
must work with synchronization intervals of 10 s.
– via Ethernet e.g. to a CP 443-1
– on PROFIBUS DP e.g. via an integrated DP master or CP 443-5 Extended
configured.
Parameters to be set for SICLOCK TM:
Path / tab
Synchronization
Input mode
Input E1
LAN general
LAN 1-5
Adr1 is given as an example. Other LAN-connections / addresses have other
parameter numbers accordingly.
LAN extra
8.2 Time stamping the input signals with IM 153-2
Parameter
(with number from the
SICLOCK parameter menu)
Mode (218)
Step pos. (219)
Step neg. (220)
Input type (230)
E1 active / passive
DCF alarm (239)
LAN timeout (349)
Adr1 protocol (e.g. 350)
Adr1 send (e.g. 351)
Adr1 def. (e.g. 352)
SNTP server (550)
Functions
Value
Ramp
Micro step
DCF
TTY passive
5
0.5 s
Layer 2 - S5
10 s
broadcast
off
135