Diagnostics
5.3 Diagnostics via Startdrive
Trigger condition: Trigger on fault
1. In order to record a time period before the trigger event, enter a value greater than 0 in
the input field for the pre-trigger.
2. Enter the recording time under "Recording duration". The maximum possible recording
duration is displayed to the right.
Should you wish to set the maximum recording time, activate the option "Use max.
recording duration".
3. Enter a recording cycle under "Cycle" The possible cycle settings depend on the number
of signals.
Additional information
Additional information on handling the trace function and the configuration and evaluation of
the trace is provided in the Startdrive online help.
5.3.2.4

Transferring the trace configuration to the device

Preconditions
● A valid trace configuration is provided in the "Traces" system folder.
● The maximum number of traces has still not been reached.
Procedure
Proceed as follows to transfer a trace configuration to the drive:
1. Open a valid trace configuration in the working area.
2. Click on icon
The "Go online" dialog is displayed if an online connection to the drive has not been
active up until now.
Here, make the settings for the online connection (also see Chapter "Establishing an
online connection to the drive (Page 127)") and click on "Connect".
Result
The trace configuration is transferred to the drive.
5.3.2.5

Activating/deactivating the trace recording

Preconditions
● An online connection has been established to the drive.
● A trace is saved in the drive.
274
.
Commissioning with Startdrive
Commissioning Manual, 12/2018, 6SL3097-5AA10-0BP0