Siemens SINAMICS S120 Commissioning Manual page 201

With startdrive
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Parameterizing encoder selection for position control
An encoder is assigned to the position control during commissioning. This encoder setting is
shown in a drop-down list at the top right in the "Mechanical system" screen form. You can
change the encoder assignment in this screen form before parameterizing the position
control. The following options are available:
1. Select the required encoder in the "Encoder system" (p2502) drop-down list.
– No encoder
– Encoder 1
– Encoder 2
– Encoder 3
2. Enter the motor revolutions for the gear ratio between the motor shaft and load shaft in
the "Number of motor revolutions" (p2504) field.
3. Enter the load revolutions for the gear ratio between the motor shaft and load shaft in the
"Number of load revolutions" (p2505) field.
4. Enter the neutral length unit LU per load revolution in the "LU per load revolution" (p2506)
field.
5. Interconnect the "Modulo correction activation" (p2577) signal source for the activation of
the modulo correction.
6. Correct the default value for axes with modulo correction in the "Modulo correction
modulo range" (p2576) field.
Parameterizing the load gearbox position tracking
If you have parameterized encoder 1 for the position control, you can set the position
tracking as follows:
1. Activate the "Activate load gearbox position tracking" (p2729.0) option.
2. Activate the desired axis type (p2720.1).
By default, the "Rotary axis" axis type is active.
3. If required, correct the number of resolvable revolutions for a rotary absolute encoder in
the "Virtual revolutions" (p2721) field.
4. If required, correct the value for the tolerance window for the position tracking in the
"Position tracking tolerance window" (p2722) field. The value is specified in whole
encoder pulses.
Examples of LU configurations
The unit LU per load revolution is a free dimension, independent of SI units, for the position
control of an EPOS axis.
The LU per load revolution upper limit is limited by the encoder resolution (rXXXX). A value
above this limit can be selected, but then not all set positions can be approached because
they may be between two encoder lines. This could result in an unsmooth axis.
Commissioning with Startdrive
Commissioning Manual, 12/2018, 6SL3097-5AA10-0BP0
4.8 Basic parameterization of the drive objects
Commissioning
199