Siemens SINAMICS S120 Commissioning Manual page 74

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Commissioning
2.2 STARTER commissioning tool
7. Select the drive unit and call the shortcut menu "Target device > Online access ...".
8. Then click on the "Address module" tab.
Assigning an IP address and a name to the drive unit
With STARTER, you can assign an IP address and a name to the PROFINET interface (e.g.
CBE20) of the drive unit. The following steps are required:
1. Connect the programming device via a Crosslink-Ethernet cable with the CBE20, inserted
2. Switch on the Control Unit.
3. Open the STARTER commissioning tool.
72
The IP address that you set must be located under "Connect to target station".
Figure 2-11
Setting online access
in the CU320-2.
Commissioning Manual, (IH1), 01/2012, 6SL3097-4AF00-0BP2
Commissioning Manual

Advertisement

Table of Contents
loading

Table of Contents