Diagnostics

3.2 Diagnostics via STARTER

LED
Color
Inputs x+1 (DI 1+, 3+, .. 19+) can be set individually via parameter p10040 (TM54F).
1)
p10040 (TM54F) = 0: Input x+1 is an NC contact.
p10040 (TM54F) = 1: Input x+1 is NO contact.
Factory setting: p10040 (TM54F) = 0 for all inputs x+1.
Single digital inputs, not fail-safe
DI x
Green
Fail-safe digital outputs with associated readback channel
F_DO y
Green
(0+..3+,
0-..3-)
Readback input DI 2y for output F_DO y (y = 0..3) at test stop.
The status of the LEDs also depends on the type of external circuit.
DI 2y
Green
3.2
Diagnostics via STARTER
The diagnostic functions support commissioning and service personnel during
commissioning, troubleshooting, diagnostics and service activities.
Prerequisite
● Online operation of STARTER.
Diagnostic functions
The following diagnostic functions are available in STARTER:
● Specifying signals with the ramp-function generator
● Signal recording with the trace function
● Analyzing the control response with the measuring function
● Outputting voltage signals for external measuring devices via test sockets
218
Status
Off
No signal at digital input x (x = 20..23)
Continuous
Signal at digital input x
light
Continuous
Output y (y=0 .. 3) carries a signal
light
Off
One of the two output lines y+ or y- or both lines of
output y carry a signal
Continuous
Both output lines y+ and y- carry no signal
light
Description, cause
Commissioning Manual, (IH1), 01/2012, 6SL3097-4AF00-0BP2
Remedy
Commissioning Manual