3.1.4.4

Terminal Module TM150

Table 3- 45
Meaning of the LEDs at the Terminal Module TM150
LED
Color
State
-
Off
Green
Continuous
light
Orange
Continuous
light
READY
Red
Continuous
light
Green/
0.5 Hz
Red
flashing
light
2 Hz
flashing
light
Green/
orange
2 Hz
or
flashing
red/
light
orange
Commissioning Manual
Commissioning Manual, (IH1), 01/2012, 6SL3097-4AF00-0BP2
Description, cause
Electronic power supply is missing or outside permissible
tolerance range.
The component is ready for operation and cyclic DRIVE-CLiQ
communication is taking place.
DRIVE-CLiQ communication is being established.
This component has at least one fault. Note:
The LED is activated regardless of whether the corresponding
messages have been reconfigured.
Firmware is being downloaded.
Firmware has been downloaded.
Wait for POWER ON.
Detection of the components via LED is activated (p0154).
Note:
Both options depend on the LED status when module
recognition is activated via p0154 = 1.
Diagnostics
3.1 Diagnostics via LEDs
Remedy
Check power supply
-
-
Remedy and
acknowledge fault
-
Carry out a POWER
ON
-