Task - Siemens SINAMICS S120 Commissioning Manual

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

2.7.1

Task

A drive in the "chassis" format in the "Vector" control mode with the following components is
to be commissioned for the first time:
Table 2- 12
Designation
Closed-loop control and infeed
Control Unit
Active Line Module
Active Interface Module
Drive 1
Motor Module
Motor
Drive 2
Motor Module
Motor
The enable signals for the infeed and the drive should be realized via terminals.
Commissioning Manual
Commissioning Manual, (IH1), 01/2012, 6SL3097-4AF00-0BP2
2.7 First commissioning, vector control mode in the chassis format
Component overview
Component
Control Unit 320-2 PN
Active Line Module 380 kW / 400 V 6SL3330–7TE36–1AAx
Active Interface Module
Motor Module 380 A
Induction motor
Without brake
With encoder
Motor Module 380 A
Induction motor
Without brake
With encoder
Commissioning
Order number
6SL3040-1MA01-0AA1
6SL3300–7TE38–4Ax0
6SL3320–1TE33–8AAx
Type: 1PL6226-xxFxx-xxxx
Rated voltage = 400 V
Rated current = 350 A
Rated power = 200 kW
Rated frequency = 59.10 Hz
Rated speed = 1750 rpm
Cooling type = non-ventilated
HTL encoder, 1024 p/r, A/B, R
6SL3320–1TE33–8AAx
Type: 1PL6226-xxFxx-xxxx
Rated voltage = 400 V
Rated current = 350 A
Rated power = 200 kW
Rated frequency = 59.10 Hz
Rated speed = 1750 rpm
Cooling type = non-ventilated
HTL encoder, 1024 p/r, A/B, R
117