Diagnostics
3.1 Diagnostics via LEDs
3.1.2.7
Smart Line Module booksize compact format
Table 3- 21
Meaning of the LEDs on the Smart Line Module booksize compact
State
RDY
DC LINK
Off
Off
Green
--
Orange
Red
Orange
Orange
Red
--
Green/red
--
(0.5 Hz)
Green/red
--
(2 Hz)
Green/orange
--
or
red/orange
Hazardous DC link voltages may be present at any time regardless of the state of the "DC
LINK" LED.
The warning information on the component must be carefully observed!
200
Electronic power supply is missing or outside
permissible tolerance range.
The component is ready for operation and cyclic DRIVE-
CLiQ communication is taking place.
The component is ready for operation and cyclic DRIVE-
CLiQ communication is taking place.
The DC link voltage is present.
The component is ready for operation and cyclic DRIVE-
CLiQ communication is taking place.
The DC link voltage is too high.
DRIVE-CLiQ communication is being established.
This component has at least one fault.
Note:
The LED is activated regardless of whether the
corresponding messages have been reconfigured.
Firmware is being downloaded.
Firmware download is complete. Wait for POWER ON.
Detection of the components via LED is activated
(p0124).
Note:
Both options depend on the LED state when activated
via p0124 = 1.
DANGER
Description, cause
Commissioning Manual, (IH1), 01/2012, 6SL3097-4AF00-0BP2
Remedy
–
–
–
Check the line voltage
–
Remedy and acknowledge
fault
–
Carry out a POWER ON
–
Commissioning Manual