Perform a learn run
Note
Ensure that 15 to 25 cm of the door's range of motion from the CLOSED position are
unobstructed during the learn run.
1. Make sure that the door is in the CLOSED position.
2. Press and hold down the learn run button (S401 / S1
3. Connect the power supply.
4. For the M4, MDG400. MDG400NMS and M5 motors, the output transmission [mm/rev]
must be configured for the initial commissioning or motor adaptation. For the M4,
MDG400 and M5 motors, set default value to 176 mm/rev. You have to press the learn
run button (S401 / S1) again and hold it down.*
* SIDOOR ATD4xxW
5. The learn run starts automatically, and the learn run button can be released. (See Table
6-13 Starting a learn run when the line voltage is applied (Page 111))
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T
System Manual, 06/2016, A2B00096162-AN
SIDOOR AT40, ATD400K, AT400S, ATD400V, ATD400W, ATD4xxW, ATD400T:
Slot X3 on the controller.
Note
SIDOOR ATD400T
Observe Section Direct voltage supply provided by customer (Page 276), subsection
"Requirements for the DC power supply (SIDOOR ATD400T)"
SIDOOR ATE250S: Slot X1000 on the controller.
Connecting and commissioning
).