Recommendations on UPS data
Output voltage
Output frequency
Output power
Wave type
Current voltage distortion
Classification (according to IEC
62040-3)
Example calculation for an M3 motor
Input data
Tag
Value
F
80 N
FR
F
60 N
HC
F
70 N
HO
I
0.1 A
O24
m
180 kg
D
N
5
C
s
0.8 m
D
T
20 s
HC
T
20 s
HO
T
310 s
STBY
v
0.3 m/s
C
A UPS with 600 W and a bridging time of 10 minutes makes approx. 30,000 J available.
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T
System Manual, 06/2016, A2B00096162-AN
230V ± 10%
47 ... 53 Hz
> 600 W
Sine
< 5% at full load
VFI
Definition
Door friction without counter-
weight
Holding time CLOSED
Holding power OPEN
External power supply 24 V
Door weight, total
Cycles OPEN/CLOSED
Door width, 1 leaf in meters
Hold time closed
Hold time open
Standstill time without holding
power
Closing speed
8.3 Uninterruptible power supply (UPS)