Input/Output Specifications - Omron EQUO Series User Manual

Air flow station, air flow sensor
Hide thumbs Also See for EQUO Series:
Table of Contents

Advertisement

<Inserting SD memory card>
<Removing the SD Memory Card>
(1) Push the inserted SD memory card inward until it clicks.
(2) Stop pushing and let the card pops out. Be careful not to drop it.
(3) "SD" on the display disappears.
Important
・If an SD memory card is unformatted, format it before inserting it into the SD card slot.
・For SD memory card format software distribution page, refer to the following URL.
https://www.sdcard.org/downloads/formatter_4/

2.3.3 Input/Output Specifications

(1)
Alarm Output
<Alarm Output Terminal>
The terminal names are inscribed on the unit.
Use the provided alarm output connector for wiring.
<Output Specifications>
External Power Supply Voltage
Load Current
ON Residual Voltage
OFF Leakage Current
Internal Circuit Diagram
Important
・Do not connect the external power supply directly between OUT and GND.
・Be sure to connect a load.
(1) OUT
Outputs the results allocated in THR mode.
(2) GND
A common terminal.
2-10
2. Part Name and Function
( *)
(1) Insert an SD memory card into the SD memory
card slot with the metal terminal facing up.
(2) Push the card inward until it clicks.
(3) "SD" appears on the display.
DC12 ~ 24 V ±10%
Max. 45 mA
Max. 1.2 V
Max. 0.1 mA
Load
External
Power
Supply

Advertisement

Table of Contents
loading

This manual is also suitable for:

D6fz-seriesD6fz-fgt seriesD6fz-fgx21D6fz-fgs1000

Table of Contents