Pulse Output/Unit Error Output
Pulse Output and Unit Error Output are available for single Air Flow Sensor operation. The
specifications are shown below:
Output method
Output Stage Circuit Diagram
Max. rated voltage
Max. rated current
Residual voltage
Leakage current
Pulse Output
Unit
error
output
(*) Can be changed by the D6FZ-FGX21 Air Flow Station.
Nch open drain output
24V DC
50 mA
Max. 1.5 V
Max. 50 μA
Outputs the measured standard flow rate in the
Output detail
corresponding unit pulse.
1, 10 (Factory default),100, 1000L/P (*)
The pulse output inverts when the half amount of
specified flow rate passes.
Output unit
(E.g. The output inverts at every 5 L is passed, if
the rate is specified to 10 L/P.)
However, if the frequency increases, the duty may
fluctuate by 20 to 80%.
Turns ON the output when any of the errors below
Output detail
occurs.
Memory error
Ultrasonic wave measurement error
Detection item
Pressure measurement error
Temperature measurement error
Power supply voltage drop detection
2-4
2. Part Name and Function
Inside D6FZ-FGS1000
Pulse Output
Unit error output