■Air Flow Station (D6FZ-FGX21)
Display
DATA
Measured data writing
E1100
failure
The unit XX integrated
SEN
standard flow rate reset
E22XX*
failure
The unit XX setting
SEN
parameter reading
E23XX*
failure
SEN
The unit XX setting
E24XX*
value update failure
SEN
Sensor Error
*
E25XX
* "XX" indicates an ID of Air Flow Sensor.
Description
Failed to write recorded data to the SD
memory card due to no free space or the card
being removed during writing. Insert a writable
SD memory card.
Hold the MODE key for 3 seconds or more to
cancel the error display.
If this error occurs, insert a normal SD memory
card and stop recording. Resume recording
after checking that the data has been normally
written to the SD memory card.
The integrated standard flow rate reset
notification is not output from the sensor unit
with the relevant ID when recording starts.
A break in connection or the discontinued
power supply to the sensor unit may be the
cause. Check the cable and reset the power
supply.
Holding the MODE key cancels the error
display.
integrated standard flow rate of the sensor
where the error occurred is not reset.
Failed to read the setting parameters from the
sensor unit whose setting is to be changed
when the unit enters FUN mode.
A break in connection, discontinued power
supply to the sensor unit or replacement of the
sensor with the power ON may be the cause.
Check the cable and reset the power supply.
Holding the MODE key cancels the error
display. FUN mode operation continues, but
the setting values of the sensor where the error
occurred is not displayed.
Failed to change the sensor setting values in
FUN or THR mode.
A break in connection or the discontinued
power supply to the sensor unit may be the
cause. Check the cable and reset the power
supply.
Holding the MODE key cancels the error
display.
continues, but the setting values of the sensor
where the error occurred are not displayed.
Failed to read measured value from unit XX
due to the sensor error. Remove the cause to
error and hold the MODE key for at least 3
seconds to cancel the error.
When
occurrence, record is also continued although
the error is displayed. And measured data of
unit XX is recorded as "ERR"
6-2
Troubleshooting
Recording
continues,
FUN
or
THR
mode
recording
at
the
.
6.Appendix
but
the
operation
time
of
error