Table of Contents

Advertisement

4.3

Settings (THR Mode Operation)

THR mode provides the following settings:
・Air Flow Sensor thresholds
・Air Flow Station alarm hold setting
Note
The setting parameters for Air Flow Sensor units are retained in individual sensor units,
and not in Air Flow Station units.
Zero Flow
The Air Flow Sensor thresholds are set to the following values by factory default:
Hi (Upper threshold)
Lo (Lower threshold)
(Leak Detection Flow Rate)
<Air Flow Sensor D6FZ-FGS1000>
The status indication changes as shown below,
Air Flow Sensor Unit Status
(1)
(2)
(3)
(4)
(5)
*1: In case of factory default setting, (3) does not occur because the lower threshold value and Leak Detection Flow
Rate are both 0L/min
*2: When the value of Momentary Standard Flow is from -0.4 to 0.4L/min, the flow consider as zero. The measured
result is in this range, the indicator shows (4).
Hi
Lo
Cut
3)
Model
D6FZ-FGS1000
1000 L/min
Cut
Indicator
Orange Blink
Green ON
Orange Slow Blink *
2
Green Slow Blink *
Deep Orange Blink
4. Setting (Air Flow Station Operation)
(1)
(2)
(3)
(4)
(5)
Backward
D6FZ-FGT500
250 L/min
0 L/min
250 L/min
0 L/min
0 L/min
The air flow rate exceeds the upper threshold value.
The air flow rate is normal and between the upper
and lower threshold values.
1
The air flow rate exceeds the lower threshold value.
The air flow rate is zero.
The rate is within the lead detection flow rate range.
The air flows backward.
4-18
D6FZ-FGT200
100 L/min
100 L/min
0 L/min
Definition