Air flow station, air flow sensor
Hide thumbs Also See for EQUO Series:
Table of Contents

Advertisement

(2)
Air Flow Sensor Connection
Up to eight* Air Flow Sensor units can be connected to an Air Flow Station.
Connect the Air Flow Sensor and Air Flow Station units as shown below:
* When the measurement data recording cycle is 2 second or longer. Up to four units when
the cycle is 1 second.
Connection Cable
Air Flow Station
(Length: 1.5 m)
D6FZ-FGX21
Important
・ The maximum extension cable length between power supply and Air Flow Sensor, between
power supply and Air Flow Station, between Air Flow Sensor and Air Flow Station, is 100 m
respectively.
・ When connecting with Air Flow Station (D6FZ-FGX21), use 24VDC power supply.
・ When the cable length is 30 to 100m between D6FZ-FGS1000 and Air Flow Station,
between D6FZ-FGS1000 and power supply, be sure to ground blue colored wire (0V)
and shield.
(1) Connect the provided connection cable to the Air Flow Station.
Insert the connection cable in the sensor head connector until it clicks.
(2) Connect the connection cable and T-branch connector (D6FZ-FC02).
Double-Sided
Connector Cable
D6FZ-JD B
T-Branch
Connector
D6FZ-FC02
Double-Sided
Connector Cable
D6FZ-JD B
Air Flow Sensor
D6FZ-FGT
Max. 8 Air Flow Units can be Connected
Connection Cable
3-6
3. Check and Preparation
T-Branch
Connector
D6FZ-FC02
Double-Sided
Connector Cable
D6FZ-JD B
Air Flow Sensor
D6FZ-FGT
T-Branch
Power Source
Connector
D6FZ-FC02
Breakout Cable
D6FZ-JD A
Double-Sided
Connector Cable
D6FZ-JD B
Air Flow Sensor
D6FZ-FGS1000
(DC24V)