09 Keyswitch
Use the Keyswitch function to use a zone as an on/off switch for the system or assigned
groups. Operating a Keyswitch zone when the system is unset starts the timed full setting
routine and the exit time is applied. The system sets when the exit time expires or a Final or
Push Set is activated.
Note: Assign a
to the Keyswitch zone function to cause the Instant setting routine to be
#
activated. In this case the exit time is not applicable. If a Keyswitch Zone has its
omit attribute enabled, activation of the Keyswitch force sets the assigned groups.
When the Keyswitch is activated twice during the exit time of an autoset, the autoset is
temporarily cancelled for a few seconds, then it restarts the exit time causing the panel to
reset.
Operating a Keyswitch zone type during the pre-warn period of an autoset starts a Force Set.
If you then activate the switch again (i.e. unset with Keyswitch) before the panel sets, the
pre-warn continues on the autoset.
Note: When the Keyswitch is activated the second time to take the panel back into pre-
warn, it can be up to 10 seconds before the pre-warn tones at the keypad start up
again.
If the system is set, operating a Keyswitch immediately unsets the assigned groups and there
is no entry time countdown.
The Part attribute of the Keyswitch function defaults to 0 (disabled) and the standard
Keyswitch function full sets the system. To part set the system using the Keyswitch, enable
the Part attribute.
Note: The operation of a Keyswitch zone can be extended to the setting and unsetting of
multiple groups by pressing
Group Function.
The standard programming of the Keyswitch function requires a momentary change from
1 k to 2 k to both set and unset the system. If the Keyswitch connected has a latching
mechanism, press
has been assigned. The Keyswitch operation is as follows: 1 k to 2 k sets the system;
2 k to 1 k unsets the system.
The Keyswitch function can also be programmed to reset alarms (refer to Keyswitch Level
[51.14]). If the Keyswitch is assigned a sufficient type to reset the alarm condition, the alarm
is cancelled and immediately reset when the Keyswitch is used to unset the system
following an alarm activation.
Note: The activated zones are not displayed on the keypad when a Keyswitch is used to
reset the alarm.
10 Secure Final
This zone has dual functionality:
When the system is setting, set or unsetting operation is identical to the Final zone
function.
when assigning a group to the zone. Refer to the Star
when assigning the function. The display indicates 09=KEYSWITCH
Program Zones [52]
97