1=No of Alarms
2=Unset Limit
3=Set Limit
Note: This feature only affects Contact ID, SIA and Microtech communication formats.
Confirm Time [51.49]
Use this option to set the maximum time between two separate zones for a confirmed alarm
to be generated up to a maximum of 99 minutes, which is equivalent to the complete set
period, with a default of 30 minutes.
Keypad Access [51.54]
Use this option to select how the keypad unsets the system. There are two options:
1=Always
2=Except Entry
Confirm Operation [51.55.1]
Use this option to control when confirmed alarms can be triggered. The choices are:
1=Before Entry
2=Except entry
3=Always
Confirm Entry Timeout [51.55.2]
Use this option to control whether exit type zones can cause confirmed alarms after an entry
timeout.
0=Disable Exits
1=Enable Exits
The total number of zone activations signalled in any one set period.
The selectable values are 0 to 10 where 0 is unlimited.
The number of activations logged from any one zone in any one unset
period. The selectable values are 0 to 10 where 0 is unlimited. The
default is 3. Fire alarms are not restricted by this parameter.
The number of activations logged from any one zone in any one set
period. The selectable values are 0 to 10 where 0 is unlimited. The
default is 3. Fire alarms are not restricted by this parameter.
Keypad always unset the system.
Except when entry time is running. This ensures that users are
unsetting using a fob or MAX tag (portable device).
Confirmed alarms can be triggered before starting entry time
only.
Confirmed alarms can be triggered any time except during the
entry delay period. (PD6662: 2004)
Confirmed alarms are always enabled. (PD6662: 2010)
Exit type zones will only cause unconfirmed intruder alarms. They will
not contribute to the two activations required for a confirmed alarm.
After the expiry of the entry delay, activation of an exit type zone will
be identical to an intruder zone.