Honeywell Galaxy Flex Installer Manual page 96

Hide thumbs Also See for Galaxy Flex:
Table of Contents

Advertisement

Program Zones [52]
03 Intruder
The Intruder function is inactive when the system is unset. When the system is set,
activation of an Intruder zone causes a full alarm activation that requires to be reset with a
code authorized for System Reset (refer to System Reset [51.6] and Reduce Reset
[51.55.3]).
All zones are programmed as Intruder by default, including the zones on RIOs that are
added to the system at a later date.
05 Security
The Security zone function is continuously operational, except that a Security zone
activation when the system is unset generates a local alarm (Horn outputs activated) that
does not require a system reset. Any valid code (type 2 or above) cancels the alarm and
resets the system. An activation in the set state generates a full alarm that requires a system
reset. The activation (+) and restoration (–) of Security zones is recorded in the event log.
07 Entry
This function initiates the unsetting procedure in the same way as a Final zone. However,
during the setting routine an Entry zone operates as an Exit zone type. This function is
normally used in conjunction with a Push Set zone, which acts as the exit terminator for the
setting procedure.
Pressing
when programming an Entry zone doubles the entry time of the group.
Opening an Entry zone during the exit time is reported on the keypad as an open zone, and
the entry/exit horns bleep rapidly to indicate that the zone is open.
08 Push Set
This zone function is used to terminate the setting routine. The system sets when the Push
Set zone, usually a push button, is activated. The entry/exit horn stops immediately when the
button is pressed and the system sets after four seconds, allowing the doors to settle to the
closed state. The Push Set zone remains inactive until the next setting routine.
Note: The Push Set zone can be either 1 k going to 2 k or 2 k to 1 k - refer to
Installation Manual (II1-0033), System Architecture for wiring details. The first time
that the Push Set is used to terminate the setting, the button needs pressing twice.
The first press identifies the normal status of the button to the system.
Activating a Push Set zone during the exit time is not reported on the keypad as an
open zone.
Note: The termination feature of a Push Set zone can be extended to terminate the setting
of multiple groups by pressing
Star
Group Function.
96
Galaxy Flex Installer Manual
when assigning a group to the zone. Refer to the

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents