The panel only requests Engineer Level Reset if alarms have been signalled via the
Communication Module and the appropriate level reset is set to 7. If no signal is transmitted,
the reset is automatically reduced to type 6. This feature is only active when the DTMF
signalling format is selected.
No. Re-Arms [51.08]
Use this option to set the number of times that an armed system can re-arm the bells
following an alarm activation. The default setting is 9 (infinite) and the range is 0 to 9.
When the option is enabled the system re-arms at the end of the programmed confirm time,
if all zones are closed or are open and can be omitted, or if the Omit all force is enabled.
The intruder output remains active until a system re-arm occurs.
Zones that are open at the end of the bell time must be omittable (Omit attribute enabled);
the re-arm will omit these zones. The complete zone circuit, including the tamper facility, is
omitted. Refer to Program Zones [52] for details on enabling the zone omit attribute.
Note: If an open zone is not omittable, then the system will not re-arm, unless parameter
09=Omit All is set to 2.
Omit All [51.09]
This option determines if activated zones can be omitted at re-arm as described above.
0=Disabled
1=Omit All
Omits any omittable zones that are open at re-arm. The complete zone
circuit including tamper is omitted.
2=Force
As Omit All but omits zones whether omittable or not. Refer to Program
Zones [52] for details on enabling the zone omit attribute.
Key "0" [51.10]
Key
on the keypad can be assigned to operate as a Push-set zone function. This terminates
0
the timed setting procedure. When the option is set to 1 (enabled), pressing
time completes the setting of the system. The default is 0 (disabled).
Note: Key
must be pressed only on the keypad used to start the setting procedure.
0
Local Part [51.11]
When the Local Part parameter is set to 0 (disabled, the default setting) the Intruder outputs
are disabled when the system is part set and the programmed bell delay is overridden. This
option is normally used to prevent the communicator from dialling the Alarm Receiving
Centre.
If the Local Part parameter is set to 1 (enabled) the Intruder outputs activate if an alarm
condition occurs when the system is part set.
Option 2 (SIA part off) is identical to option 1 with the exception that when the alarm
format of the telecom module is set to SIA, part setting and unsetting of the system is not
signalled to the ARC. You can assign a different value to each group.
Parameters [51]
during the exit
0
75