Diagnostics [61]

Engineer 2

Diagnostics [61]
Use this option to run these diagnostic tests:
the communication integrity between the panel and modules
voltage measurements
resistance measurements
module version checks
panel memory checks
fuse checks
This option is split into two sections:
Latest: providing real time diagnostic information for the system.
Historical: a snapshot of the system diagnostic status can be generated and saved.
Latest [61.1]
The Diagnostic options are:
1=MEMORY TEST
2=KEYPAD COMMS the communication level between the panel and the keypads.
3=RIO COMMS
4=PSU COMMS
5=MAX COMMS
6=COMM MODULES the communication level between the panel and the Int Telecoms,
158
this option forces a check of the panel memory.
the voltage and version at each RIO as well as the communication
level between the panel and the RIO.
the voltage at each Power Supply Unit and the communication
level between the panel and the SPSUs. It is identical to the RIO
COMMS diagnostic with the exception that it also indicates the
fuse status and battery status. A number to the right of the current
indicates a blown fuse:
2=Battery fault
3=+12V Auxiliary 1 fault
4=Not Used
5=Not Used
6=Not Used
A
indication means low battery or a missing battery.
95%
2 13.6V
the communication level between the panel and the MAX/DCM
readers.
Ethernet/GPRS, ISDN, GSM, the USB, and the Audio Module.