X2 Profinet - Siemens Sinumerik 828D Manual

Ppu and components
Hide thumbs Also See for Sinumerik 828D:
Table of Contents

Advertisement

Anschließbare Komponenten
7.8 PP 72/48D PN
Wiring the screw terminal block
The required 24 VDC load power supply is wired to the screw-type terminal block (X1).
Protective separation
The 24 V direct voltage must be configured as an extra-low-voltage with protective separation
- DVC A or PELV.
Power cables
Table 7-69
Features
Connection option
Current carrying capacity
Max. cable length
Use flexible cables with a cross-section of 0.25 to 2.5 mm
the power supply according to the maximum occurring current.
If you only use one wire per connection, a ferrule is not required.
You can use ferrules without an insulating collar in accordance with DIN 46228, Form A long
version.
7.8.3.2

X2 PROFINET

Requirement
The I/O module has certified PROFINET interfaces, however their functionality cannot be fully
utilized within the scope of the SINUMERIK 828D control system. Networking within
SINUMERIK 828D is performed via a PLC I/O interface, which is based on PROFINET.
Data transmission rate and cables
The interfaces are designed for full-duplex mode; in other words, the ports can both transmit
and receive. When connecting I/O modules to the SINUMERIK 828D, please use the
preassembled SINAMICS DRIVE-CLiQ signal cables; from a technical point of view, these are
also suitable for use with PROFINET:
● Article number: 6FX2002-1DC00-...
● The transmission characteristics of these cables meet the requirements of CAT5.
● Data transmission speed: 100 Mbps (fast Ethernet).
● The maximum length of the connections between the end device and network component
or between two network components (e.g. switch ports) must not exceed 70 m.
200
DANGER
Cable specification for X1
Version
Up to 2.5 mm
2
max. 10 A
10 m
(or AWG 23 to AWG 13) for wiring
2
Manual, 05/2015, 6FC5397-2DP40-3BA4