G1 Ro Features - Culligan G1 Series Installation, Operation And Service Instructions

Reverse osmosis water treatment systems
Table of Contents

Advertisement

G1 RO Features

The Series G1 Reverse Osmosis systems are the direct result of Culligan's long time experience in membrane appli-
cations around the world. From process water for any size business to treating water for an entire city, Culligan has the
knowledge and the range of products you need to get the job done.
The Series G1 reverse osmosis system is sized to serve many small-to-medium-sized applications that require high-qual-
ity reverse osmosis water. It is designed with the flexibility to closely match your treatment requirements from 0.35 to 2.8
gallons per minute (500 to 4,000 gallons per day). Mount the system on a wall to save floor space, or install it on the floor
using an optional floor stand. A rich standard feature set with multiple options can satisfy virtually any application. Select
the right size and choose any options needed to complete your system.
Key G1 RO System Features
• Simple System Integration
• Global Product Platform
• Flexible Configurations
• Quick Delivery/Easy Installation
• Exclusive Culligan Advanced Electronics
• Multiple Languages
• Historical Operating Data
• Alarm Recognitions
• US Standard and Metric Readings
• Remote Monitoring Options for connection to a control room PLC
• Telemetry Options
• Real Time Clock: tracks date and time has five-year battery back up.
• TDS Probe: TDS probe measures product water quality.
• Remote Alarm Output Connection (Optional): Provides either a N.O. or N.C. Dry Contacts. This feature can be
used to activate an alarm or programmed into a customers (DCS) building alarm system.
GBE RO Controller Features
System Computes Normalized Flow
The system computes normalized flow and can be set to trigger an alarm if the normalized flow drops below a specified
limit.
Power Up Mode
The system can be configured to either go to standby mode or to automatically return to making RO water in the event of
power loss and restoration.
Storage Tank and Pressure Logic
The system has the ability to monitor high and low level switches in an atmospheric storage tank and a pressure switch in
a pressurized storage tank to automatically put the system into standby mode when the tank is full.
Pretreatment Lockout
Allows for single softener or filter pretreatment that can be set to go into regeneration or backwash cycle at low water use
periods and have the RO in standby until cycle is completed. RO product water tank would need to be sized correctly
based on flow demand if continuous RO product water is required.
GBE Historical Data
The GBE RO Controller stores basic performance data over the lifetime of the membranes as an aid to optimizing RO
performance and determining when the membranes need to be cleaned or replaced.