First Time Setup With Wireless Remote, High And Low Float Switches; Set Up Groc-Remote Communication; Set Up Float Switches; Set Up Units Of Measure/Initialize System - Culligan G1 Series Installation, Operation And Service Instructions

Reverse osmosis water treatment systems
Table of Contents

Advertisement

First Time Setup with Wireless Remote, High and Low Float Switches

Press
to select a setting. Press
Select Language
LANGUAGE
ENGLISH
Select the controller language.
FIRST TIME SETUP
From the FTS screen, press
PRESS DOWN ARROW
settings.
Set Up Date
JAN
SET
MONTH
Set the Month, Day, and Year.
1
SET
DAY
SET YEAR
2012
Set Up Clock Type and Time
CLOCK TYPE
Select either a 12-hour clock
12 HR
(12:00A–11:59P) or 24-hour
clock (00:00–23:59)
SET HOUR
NOTE
12PM
1
SET
MINUTES
Set Up System Status at Startup
POWERON MODE
Select the system status at
OFFLINE
startup—offline or running. You
can change status after setup.

Set Up Units of Measure/Initialize System

SYSTEM UNITS
US INCH
Select METRIC for units out-
side the United States.
RUNNING
The "home" screen displays
JAN-01-12
12:01P
the RUNNING or OFFLINE
status of the RO system.
Cat. No. 01021713
or
to change the setting. Press
to scroll to the date/time
24-hour clock
format does not
require AM or PM
to save. Press

Set Up GROC-Remote Communication

>1)WIRELESS REM
From the main menu, select
2)MODEM
4)SETUP —> 5)ACCESSO-
3)FLOW METERS
RIES —> 1)WIRELESS REM.
4)SWITCH INPUTS
WIRELESS REM
Change the setting to
NOT INSTALLED
INSTALLED.
CHANNEL #
Select the channel to com-
1
municate between the remote
and the RO controller.
RF FREQUENCY
Select the radio frequency:
915MHz
915MHz for North America,
869 or 933 in other locations.

Set Up Float Switches

2)LANGUAGE
From the SETUP menu, select
3)POWERON MODE
4)FLUSH MODES
5)ACCESSORIES.
>5)ACCESSORIES
1)WIRELESS REM
2)MODEM
Select 4)SWITCH INPUTS.
3)FLOW METERS
>4)SWITCH INPUTS
FLOAT SWITCHES
Scroll to the FLOAT
NORMALLY OPEN
SWITCHES setting; select
NORMALLY OPEN.
10
FS Hi
Select how long the float
Delay
switch stays closed after tran-
sitioning from high to low level.
MINUTES
Press
to save the settings and return to the
home screen.
Set Up GROC-Remote Communication
>1)RF SETUP
From the main menu, select
2)MODEM SETUP
2)SETUP —> 1)RF SETUP.
CHANNEL #
Select the SAME channel to
1
communicate that is set on the
RO controller.
RF FREQUENCY
Select the radio frequency:
915MHz
915MHz for North America,
869 or 933 in other locations.
to exit from a menu.
Quick Programming Guide
127

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

G1-2sG1-3lG1-4lG1-1fG1-2fG1-3s ... Show all

Table of Contents