5.2

Restoring the factory settings

If nothing else works, restore the factory settings!
You can restore the factory settings using parameter P0970.
Parameter or proce-
dure
P0003 = 1
P0010 = 30
P0970 = 1
IOP - select factory
restart from the extras
menu.
STARTER
Note
Data transfer is interrupted while the factory parameter settings are being restored.
The following parameters remain unchanged even after the factory settings have been
restored:
• P0014 Storage mode
• P0100 Europe / North America
• P0201 Power stack code number
• Communication parameters
• Power-Module-specific data
SINAMICS G110D
Operating Instructions, 07/2016, FW V3.63, A5E36768472B AB
Description
User access level
1: Standard level
Commissioning parameter
30: Factory setting, parameter transfer
Restore factory settings
1: Restore the factory parameter settings
The IOP will display a message stating that a factory reset is taking place
and display a progress bar. When completed the display will display a mes-
sage that the factory reset has been successfully completed.
Displays a progress bar.
Commissioning
5.2 Restoring the factory settings
63