Commissioning
5.5 Factory settings for the Inverter
Parameter Factory setting Meaning of the factory setting
P0335
0
P0625
20
P0640
200
P0700
6
P0727
0
P0970
0
P1000
3
P1080
0
P1082
50
P1120
10
P1121
10
P1300
0
P3900
0
68
Non-ventilated: Shaft-mounted fan
in the motor
°C
[%]
6 (default setting)
DI0: On / off
DI1: Direction reversal
Blocked
Fixed frequencies
[Hz]
[Hz]
[s]
[s]
V/f control with linear characteristic Control mode
No quick commissioning
Function
Motor cooling (specify the motor cooling
system)
Ambient temperature of motor
Motor overload factor (entered in % referred
to P0305)
Select the command source
Control response when the motor starts
(start, stop, reverse)
Restore factory settings
Select the source of the frequency setpoint
(setpoint input)
Minimum frequency
Maximum frequency
Ramp-up time
Ramp-down time
Completes the quick commissioning.
Operating Instructions, 07/2016, FW V3.63, A5E36768472B AB
Access
level
2
3
2
1
3
1
1
1
1
1
1
2
1
SINAMICS G110D