Functions
6.3 Command sources
6.3
Command sources
6.3.1
Selecting command sources
Selecting the command source [P0700]
The motor is switched on/off via external inverter control commands. The following command
sources can be used to specify these control commands:
● Operator Panel - automatically handled when HAND mode is selected
● Digital inputs
● Fieldbus
The command sources available depend on the inverter version.
● For inverters with a fieldbus interface, the 'fieldbus' (P0700 = 6) is pre-selected as the
command source,
Table 6- 13
Parameters
P0700 = ...
102
Parameters, to select the source for the inverter control commands
Description
0: Factory default setting
2: Digital inputs (P0701 ... P0705)
4: USS at RS 232
6: Fieldbus (P2050 ... P02091) default setting.
Operating Instructions, 07/2016, FW V3.63, A5E36768472B AB