Connection
4.7 SINAMICS G110D Specifications
The inverter is suitable for use on a circuit capable of delivering the short circuit current
shown in the tables below when protected by the branch circuit protection indicated.
Table 4- 5
SINAMICS G110D model no.
Table 4- 6
Branch circuit protection with circuit breakers (DIVQ)
SINAMICS G110D model no.
6SL3511-.PE17-5AM.
6SL3511-.PE21-5AM.
6SL3511-.PE23-0AM.
6SL3511-.PE24-0AM.
6SL3511-.PE25-5AM.
6SL3511-.PE27-5AM.
44
Non-semiconductor fuses better than RK5 (JDDZ)
6SL3511-.PE17-5AM.
6SL3511-.PE21-5AM.
6SL3511-.PE23-0AM.
6SL3511-.PE24-0AM.
6SL3511-.PE25-5AM.
6SL3511-.PE27-5AM.
Max current rating of circuit
breaker (A)
15
15
25
35
45
60
Max current rating of fuse (A)
10
15
25
30
30
30
Circuit breaker types
3RV1742
3RV2711
LGG
CED6
3RV1742
3RV2711
LGG
CED6
3RV1742
3RV2721
LGG
CED6
3RV1742
3RV2721
LGG
CED6
65 kA, 480 V AC
50 kA, 480 Y / 277 V AC
65 kA, 480 V AC
65 kA, 480 V AC
65 kA, 480 V AC
50 kA, 480 Y / 277 V AC
65 kA, 480 V AC
65 kA, 480 V AC
Operating Instructions, 07/2016, FW V3.63, A5E36768472B AB
SINAMICS G110D SCCR with
fuse
100 kA, 480 V AC
100 kA, 480 V AC
100 kA, 480 V AC
100 kA, 480 V AC
100 kA, 480 V AC
100 kA, 480 V AC
SINAMICS G110D SCCR
with circuit breakers
65 kA, 480 V AC
65 kA, 480 Y / 277 V AC
65 kA, 480 V AC
65 kA, 480 V AC
65 kA, 480 V AC
65 kA, 480 Y / 277 V AC
65 kA, 480 V AC
65 kA, 480 V AC
65 kA, 480 V AC
50 kA, 480 Y / 277 V AC
65 kA, 480 V AC
65 kA, 480 V AC
65 kA, 480 V AC
50 kA, 480 Y / 277 V AC
65 kA, 480 V AC
65 kA, 480 V AC
65 kA, 480 V AC
50 kA, 480 Y / 277 V AC
65 kA, 480 V AC
65 kA, 480 V AC
65 kA, 480 V AC
50 kA, 480 Y / 277 V AC
65 kA, 480 V AC
65 kA, 480 V AC
SINAMICS G110D