Parameters With Follow-On Parameterization; Frequently Required Parameters - Siemens SINAMICS G110D Operating Instructions Manual

Distributed converter
Hide thumbs Also See for SINAMICS G110D:
Table of Contents

Advertisement

2.2.3

Parameters with follow-on parameterization

When you change certain parameters, the system may automatically change other
parameters accordingly. This makes it much easier to parameterize complex functions.
Example: Parameter P0700 (command source)
Parameter P0700 can be used to switch the command source from the fieldbus to digital
inputs. When the value of P0700 is changed from 6 (command source "fieldbus") to 2
(command source "digital inputs"), other parameter values are changed automatically:
● New functions are assigned to the digital inputs (P0701 ... P0704)
● Inverter control is interconnected with the signals from the digital inputs (P0800, P0801,
P0840, etc.)
For more information about follow-on parameterization for P0700, see the List Manual.
2.2.4

Frequently required parameters

Parameters that in many cases help
Table 2- 1
This is how you filter the parameter list to keep the number of displayed parameters to a minimum
Parameter
Description
P0003 =
User access level
1: Standard: Allows access to the most frequently used parameters (factory setting)
2: Extended: Extended access, e.g. to inverter I/O functions
3: Expert: To be used by experts
P0004 =
Parameter filter
0: All the parameters are displayed (factory setting).
2: Inverter
3: Motor - data of the motor and output filter are displayed
Table 2- 2
How to switch to commissioning mode or restore the factory setting
Parameter
Description
P0010 =
Commissioning parameters
0: Ready (factory setting)
1: Perform quick commissioning
30: Factory setting - initiate restore factory settings
Table 2- 3
How to determine the firmware version of the Control Unit
Parameter
Description
r0018
The firmware version is displayed:
SINAMICS G110D
Operating Instructions, 07/2016, FW V3.63, A5E36768472B AB
2.2 Adapting the Inverter to the application
Introduction
21

Hide quick links:

Advertisement

Table of Contents
loading