Programmable process images
It is possible, using BICO, to change the functionality of both input and output process
images, with the exception of the CTT2 serial channel present in Slave 1. This serial channel
is required to be present in order that Slave 1 appears correctly on the AS-i network. The
default settings for both single slave and dual slave modes are given in the tables below.
Table 6- 58
Default input process image (slave to master) - Dual slave mode
Bit
Usage
Slave 2
DI0
Ready
DI1
Motor active
DI2
Digital input 1
DI3
Digital input 2
Slave 1
DI0
Digital input 3
DI1
Digital input 4
DI2
Serial clock in
DI3
Serial data in
SINAMICS G110D
Operating Instructions, 07/2016, FW V3.63, A5E36768472B AB
Description
0: Inverter is not responsive to AS-i master
1: Inverter is ready to respond to commands from the AS-i master
0: Inverter motor outputs are high impedance
1: Inverter motor outputs are active
0: Input 1 is inactive
1: Input 1 is active
0: Input 2 is inactive
1: Input 2 is active
0: Input 3 is inactive
1: Input 3 is active
0: Input 4 is inactive
1: Input 4 is active
Clock signal for CTT2 data transfer to AS-i master
Data signal for CTT2 data transfer to AS-i master
6.11 Operation in fieldbus systems