Siemens SINAMICS G110D Operating Instructions Manual page 204

Distributed converter
Hide thumbs Also See for SINAMICS G110D:
Table of Contents

Advertisement

Service and maintenance
7.4 Repair switch
Function
When the Repair switch is set to OFF, all power to the motor is terminated. The Inverter
pulses are disabled and the motor cannot be started or react in anyway to commands from
the Inverter or the controlling PLC. With the mains are isolated fault F0003 will be generated.
The Repair switch can be padlocked into position so that once it has been switched off, it
cannot be accidentally switched on.
The motor can be repaired or replaced as required. Once the Repair has been completed
the Repair switch can be unlocked and switched on - the motor is then directly under the
command of the Inverter or the controlling PLC.
It should be noted that although the motor is isolated, communications and commands can
be passed between the controlling PLC and the Inverter, for example, parameters can be
changed.
204
Operating Instructions, 07/2016, FW V3.63, A5E36768472B AB
SINAMICS G110D

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents