4.2.5

Parameterization of the ON/OFF 1 command

The ON/OFF command can be output from various sources. It can be realized from
the interface, from the operator panel, from the terminal strip or from a pushbutton
in the door. The ON command should be switched high active from these sources;
the commands for OFF1, OFF2 and OFF3 are always low-active (wire-breakage-
proof), and connected in series. The individual OFF commands are negated in the
SIMADYN D configured software. If OFF2 or OFF3 are used, the inputs in FP-IO
D30.X1 / P136 and D30.X2 / P137 for OFF2
D50.X1 / P138 and D50.X2 / P139 for OFF3
must be appropriately assigned: 1 = Profibus interface active
OFF3 can only be activated via the Profibus interface.
The connections are made via terminal strip X100 when selecting the "ON/OFF via
terminal strip" function.
X100:33A/33C ON
X100:34A/34C OFF1
X100:35A/35C OFF2
The ON/OFF1 pushbutton in the door is only effective, if the key-actuated switch in
the door is in the "Local" setting (refer to Section 4.2.7).
If the key-actuated switch is in the "Remote" setting, then terminal strip X100 must
be selected as source for the ON/OFF1 command (factory setting).
The assignment of the source for the ON/OFF1 command can be modified by
assigning D10.X1 / P134 ("Remote" setting of the key-actuated switch) or D10.X2 /
P135 ("Local" setting of the key-actuated switch):
1 = Profibus DP interface
2 = Operator panel OP
3 = Terminal strip X100
4 = ON/OFF! using the switch in the door
In order to activate OFF1 via the Profibus interface, depending on the particular
requirement, in addition, C138.I1 / P126 ("Remote" setting of the key-actuated
switch) or C138.I2 / P127 ("Local" setting of the key-actuated switch) must be set
to 1.
In order to activate OFF1 via the operator panel, depending on the particular
requirement, in addition, C158.I1 / P130 ("Remote" setting of the key-actuated
switch) and C158.I2 / P131 ("Local" setting of the key-actuated switch) must be set
to 1.
Siemens AG
6SE8004-0BH76
SIMOVERT MV
Commissioning Instructions
3 = Terminal strip active
4 = Profibus and terminal strip interface active
51