10 Troubleshooting
No.
Name
W 853 Sic1PvVtgHi
W 854 Sic1PvVtgLo
W 855 Sic1TmpLo
W 856 Sic1TmpHI
W 857 Sic1ComLoss
W 861 Sic2BatShort
78
SI30M-44M-60H-80H-BE-en-33
Level Cause
1
PV charge controller 1 PV
generator overvoltage: PV
voltage at the Sunny Island
Charger 1 is too high.
1
No PV voltage or short cir-
cuit on PV charge con-
troller 1: No PV voltage at the
Sunny Island Charger 1 or there
is a short circuit.
1
Sensor error (or undertem-
perature) for the PV charge
controller 1 charger temper-
ature: Sunny Island Charger 1
reports battery undertempera-
ture.
1
PV charge controller 1 de-
vice overtemperature: Sun-
ny Island Charger 1 reports bat-
tery overtemperature.
1
No communication with DC
charger for more than 24 h
– PV charge controller 1: Last
communication with the Sun-
ny Island Charger 1 was more
than 24 hours ago.
1
Battery reversely connected
or short circuit on PV charge
controller 2: Connection of the
battery to the Sunny Island
Charger 2 is reverse-poled or
there is a short circuit.
SMA Solar Technology AG
Corrective measures
• Contact the Service, if required (see
Section 16 "Contact", page 161).
• Contact the Service, if required (see
Section 16 "Contact", page 161).
• Set the Sunny Island Charger to the
operating mode "SMA
operation" (see the Sunny Island
Charger charge controller
installation manual).
• Ensure that the configuration of the
Sunny Island Charger charge
controller with the DIP switches is
correct.
• Ensure that the communication
interfaces are correctly inserted in
the Sunny Island.
• Ensure that undamaged CAT5e
cables are used for communication
and that the cables are plugged in
correctly.
• Ensure that the configuration of the
Sunny Island Charger charge
controller with the DIP switches is
correct.
• Ensure that the communication
interfaces are correctly inserted in
the Sunny Island.
• Ensure that the battery is correctly
connected to the DC connection of
the Sunny Island Charger charge
controller.
• Disconnect the PV array from the
Sunny Island Charger and restart
the system. This will ensure that the
PV array is not short-circuited.
Operating Manual