13 Parameters in Sunny Remote Control
No.
Name
223.07
BatPro3Soc
223.08
BatProTmm
224# BatSilent
No.
Name
224.01
BatSilentEna
224.02
BatSilentTmFlo
224.03
BatSilentTmMax Maximum duration of en-
225# Current Sensor
No.
Name
225.01
BatCurSnsTyp
225.02
BatCurGain60
225.03
BatCurGain50
225.04
BatCurAutoCal
128
SI30M-44M-60H-80H-BE-en-33
Description
Battery SOC for protection mode level 3
as % (expert mode)
Minimum time (in minutes) during which
there is no battery current for switching to
battery protection mode (expert mode)
If the minimum time has elapsed and no
battery current was present, the Sunny Is-
land can switch to battery protection
mode.
Description
Energy-saving mode
Time until switchover to
energy-saving mode (h)
ergy-saving mode (h)
Description
Type of battery current
sensor
A
60 mV type in
/
60 mV
A
50 mV-Typ in
⁄
50 mV
Automatic calibration of
external battery current
sensor
Value
0% to 70%
1 min to 20 min
Value
Explanation
Enable
Enable
Disable
Disable
1 h to 48 h
–
1 h to 168 h
Value
Explanation
None
No sensor is
connected.
60 mV
60 mV type
50 mV
50 mV type
A
0
⁄
to
60 mV
A
1800
⁄
60 mV
A
0
⁄
to
50 mV
A
1800
⁄
50 mV
Start
Start automatic
calibration
SMA Solar Technology AG
Default
Value
✖ ✓ 10 %
✖ ✓ 5 min
Default
value
✖ ✓ Disable
✖ ✓ 3 h
✖ ✓ 12 h
Default
value
✓ ✓ None
–
✓ ✓ 100
–
✓ ✓ 100
✓ ✓
Operating Manual
A
⁄
60 mV
A
⁄
50 mV
–