SMA SUNNY ISLAND 3.0M Operating Manual page 138

Sunny remote control
Hide thumbs Also See for SUNNY ISLAND 3.0M:
Table of Contents

Advertisement

13 Parameters in Sunny Remote Control
No.
Name
234.11
GnErrStpTm
234.12
GnWarmTm
234.13
GnRvPwr
234.14
GnRvTm
234.15
GnCtlMod
234.20
GnAlSns
234.41
GnCurCtlMo
d
234.42
GnAIFac
138
SI30M-44M-60H-80H-BE-en-33
Description
Idle time after generator
error in hours (expert
mode)
Warm-up time in seconds 5 s to 900 s
Maximum reverse power
for voltage monitoring of
generator in W (expert
mode)
Time for reverse power
or reverse current for
voltage monitoring of
generator in s (expert
mode)
Type of generator cur-
rent limitation (expert
mode)
The generator control
limits the consumption of
generator current.
Anti-islanding Sensitivity
of the generator fault
recognition (expert
mode)
Enable I‑Loop in genera-
tor operation (expert
mode, only with
SI6.0H-11 and
SI8.0H-11)
I‑Loop enables genera-
tors with inadequate volt-
age regulation to be
used in the system.
Anti-islanding factor in
current-controlled gener-
ator operation with I-
Loop (expert mode)
Value
Explanation
0 h to 24 h
0 W to 5000 W
One Sunny Island
or single-cluster
system
0 W to 20000 W
Multicluster sys-
tem
0 s to 900 s
Cur
Fixed threshold
for current limita-
tion
CurFrq
Frequency-depen-
dent current limi-
tation
Low
Low
Medium
Medium
Standard
Standard
High
High
Droop
Standard genera-
tor operation with-
out I‑Loop
CurCtl
Current-controlled
generator opera-
tion with I‑Loop
0.00 to 1.00
SMA Solar Technology AG
Default
Value
✖ ✓ 1 h
✖ ✓ 60 s
✖ ✓ 100 W
100 W
✖ ✓ 30 s
✖ ✓ Cur
✖ ✓ Standard
✖ ✓ Droop
✖ ✓ 0.10
Operating Manual