13 Parameters in Sunny Remote Control
No.
Name
261.04
SlfCsmpSpnt
261.05
SlfCsm-
pLodShed
* The parameter is visible until firmware version 3.5 of the Sunny Island. Firmware version 3.5 of Sunny Island can only be used in
multicluster systems with the Multicluster-Box 12 of device type MC-BOX-12.3-20.
262# BatUsage
No.
Name
262.01
ProtResSOC
262.02
BatResSOC
262.03
BUResSOC
148
SI30M-44M-60H-80H-BE-en-33
Description
Value
Specification of the
≤ 0 W
control target at ac-
0 W
tive self-consumption
in W*
≥0 W
Activation of load
Disable
shedding during
self-consumption.*
Enable
Description
Value
Lower limit of the
10% to 20%
deep-discharge pro-
3% to 20%
tection range for dis-
connection (%) of
the battery capacity
(expert mode)
Minimum width of
2% to 50%
the deep-discharge
protection range (%)
of the battery ca-
pacity (expert
mode)
Minimum width of
0% to 100%
the backup power
supply range on the
longest day of the
year as a percent-
age of the battery
capacity (expert
mode)
SMA Solar Technology AG
Explanation
Negative value: grid feed-in
No grid feed-in and pur-
chased electricity
Positive value: purchased
electricity
Load shedding during self-
consumption is deactivated.
Load shedding during self-
consumption is activated.
Explanation
Lead-acid batteries
Lithium-ion batteries
Lithium-ion battery, self-con-
sumption only
Lithium-ion battery, battery
backup system
Lead-acid battery, self-con-
sumption only
Lead-acid battery, battery
backup system
Default
Value
✓ ✖ 0 W
✓ ✖ Enable
Default
Value
✓ ✖ 10 %
✓ ✖ 3 %
✓ ✖ 2 %
✓ ✖ 10 %
✓ ✖ 30 %
✓ ✖ 5 %
✓ ✖ 0 %