SMA SUNNY ISLAND 3.0M Operating Manual page 143

Sunny remote control
Hide thumbs Also See for SUNNY ISLAND 3.0M:
Table of Contents

Advertisement

SMA Solar Technology AG
241.01 Rly1Op: Operating mode of the multifunction relay 1
Value
Explanation
GndSwt
Triggering of the grounding in the battery backup system
GriRdtSwt
Triggering of redundant contactor for grid disconnection in the battery backup system
242# Load
No.
Name
242.01
Lod1SocTm1Str
242.02
Lod1SocTm1Stp Battery state of charge limit for end of
242.03
Lod1SocTm2Str
242.04
Lod1SocTm2Stp Battery state of charge limit for end of
242.05
Lod1Tm1Str
242.06
Lod1Tm2Str
242.07
Lod2SocTm1Str
242.08
Lod2SocTm1Stp Battery state of charge limit for end of
242.09
Lod2SocTm2Str
Operating Manual
Description
Battery state of charge limit for start of
load shedding 1 in the standard addi-
tional time period as %
This is the valid threshold without the
additional time period.
load shedding 1 in the standard addi-
tional time period as %
This is the valid threshold without the
additional time period.
Battery state of charge limit for start of
load shedding 1 in additional time pe-
riod as %
load shedding stop in additional time
period as %
Start time of the standard additional
time period for load shedding 1 in
hh:mm:ss; corresponds to the end time
of the additional time period
Start time of the additional time period
for load shedding 1 in hh:mm:ss
Battery state of charge limit for start of
load shedding 2 in the standard addi-
tional time period as %
This is the valid threshold without the
additional time period.
load shedding 2 in the standard addi-
tional time period as %
This is the valid threshold without the
additional time period.
Battery state of charge limit for start of
load shedding 2 in the standard addi-
tional time period as %
13 Parameters in Sunny Remote Control
Value
1% to 242.02
Lod1SocTm1Stp
242.01
Lod1SocTm1Str to 90%
1% to 242.04 
Lod1SocTm2Stp
242.03
Lod1SocTm2Str to 90%
00:00:00 to 23:59:59
00:00:00 to 23:59:59
1% to 242.08 
Lod2SocTm1Stp
242.07 
Lod2SocTm1Str to 90%
1% to 242.10 
Lod2SocTm2Stp
SI30M-44M-60H-80H-BE-en-33
Default
Value
✓ ✓
30 %
✓ ✓
50 %
✓ ✓
30 %
✓ ✓
50 %
✓ ✓
✓ ✓
✓ ✓
30 %
✓ ✓
50 %
✓ ✓
30 %
143